Optimizing Façade Retrofits: Improve the Frame as Well as the Glass

In the United States, we have a façade-retrofit problem—or opportunity—depending on how you look at it. According to the U.S. Department of Energy, about 2.4 million commercial buildings, approximately 40% of the commercial building stock, have single-pane, non-thermally broken fenestration. Yet, the retrofit rate is less than 1% annually.

Retrofitting façades can be logistically and technically challenging, have a high degree of risk because of unknown concealed conditions, and be expensive relative to other energy-saving options such as lighting and HVAC upgrades. The Façade Tectonics Institute’s (FTI) barrier study illustrated these challenges (see Figure 1).

Figure 1: Barriers to retrofit. Credit: Façade Tectonics Institute.

Glazing Solutions

When façade retrofits are explored, the focus is often on improving glass performance rather than the frames. Building owners and occupants typically have no interest in reducing daylight entering their buildings—in fact, frequently it’s the opposite. To improve fenestration performance, several methods are often evaluated, commonly concentrating on the vision area:

  • Secondary glazing solutions contain a single-pane, an insulating glass unit (IGU) or potentially a vacuum insulating glass (VIG), in a sash that attaches over the top of the existing glazing either on the room-side or the exterior;
  • Solar control films are applied to the room-side or exterior-side of the existing glass to reduce thermal transmittance and solar heat gain through the glass;
  • Thin triple-pane insulating glass reproduces triple glazing performance in the weight and thickness of a double-pane IGU by using a very thin center pane; and
  • VIG improves on glass thermal performance further by creating a vacuum in the cavity between the panes, which is more highly insulating than inert gas-filled cavities. The weakest link thermally is the VIG’s edge seal, which is typically quite conductive and reduces the thermal performance of the unit. Using VIG as the room-side lite of a dual-pane IGU improves the center-of-glass (COG) U-factor further and reduces the conduction at the edge if a warm-edge spacer is utilized.

While these solutions each do a good job of reducing the heat flow through the glass, they do little, if anything, to reduce the heat flow through the frames. Typically, older aluminum frames are non-thermally broken, creating a superhighway for heat flow— from inside to outside in the winter and from outside to inside in the summer.

Sarah Sinusas, PE, is associate principal and associate executive director of practice development at WJE.

Strategies for Frame Retrofit

I recently had the opportunity to discuss retrofit projects with Sarah Sinusas, PE, of Wiss, Janney, Elstner Inc. (WJE). Sinusas is associate principal and associate executive director of practice development at WJE in its Connecticut office. She has more than 15 years of experience in enclosure consulting, including forensics and façade renovation. Sinusas and I serve on the board of the Insulating Glass Certification Council (IGCC) together. We have built a strong rapport over our shared passion for higher-performance façades.

Sinusas shared the biggest challenges she encounters with retrofits:

  • Understanding the owner’s expectations and priorities – For example, what is the acceptable balance of energy savings and occupant comfort, disruption to occupants during the retrofit and budget?
  • Understanding the context of the existing system – What can be taken apart? What can be modified? How much added load can the existing structure manage? How can the system be accessed? Site accessibility is also important to understand. Is the building occupied? Does the retrofit have to be phased or can it happen at once?
  • Identifying solutions that improve thermal performance – She noted, “It is easy to say, ‘replace the window or glass,’ but it is not always that simple.” The key is in optimizing the bang-for-the-buck. This is typically an iterative process that must consider the owner’s constraints, such as access, maintenance and what can change inside the building and on the exterior.

Custom Polyamide Profiles for Frame Retrofits

Sinusas gave an example of a retrofit project on which she and her team had collaborated with Technoform to develop a retrofit solution to thermally improve an existing non-thermally broken curtainwall. The project involved a 22-story office building with a 1960’s curtainwall containing monolithic clear glass. A bronze solar-control film had been applied on the room-side in the 1990s, along with an exterior wet-sealing using pre-formed silicone sheets and silicone sealant.

For the renovation, they selected VIG, comprising two 4-millimeter (mm) lites as the replacement for the existing monolithic 6 mm glass. They had determined the system’s structural capacity was insufficient to take significant additional weight without needing to address the structural anchorage. They also knew that, while VIG provided a very good solution for reducing heat flow through the glazed area, it would not impact heat flow through the frame.

The existing frame could be considered an effective thermal radiator. Sinusas described the mullion structure as being expressed at the exterior of the building in a “T” shape. This T-shape runs the length of the verticals, with no thermal barrier to the inside elements. This resulted in a continuous thermal “radiator” on the exterior, with no mechanism to reduce heat flow. (See the jamb section in Figure 3 and the associated THERM analysis). As Sinusas said in a presentation, “When it’s cold outside, it is cold inside.” The glass was interior glazed and held in place with glazing stops.

Figure 3: The plan view of the curtainwall’s vertical mullion and the associated THERM analysis showing the temperature profile from inside to outside. Credit: WJE.

Because of the existing design, the exterior mullion and the U-channel aluminum angle to which it connects and which extends to the inside, could not be removed. This caused a major heat loss mechanism that needed to be mitigated.

To reduce the thermal transfer, the team evaluated over 20 different redesign options, focusing on creating a thermal barrier on the inside of the curtainwall, which they planned to hide beneath a new interior mullion cover. Modifying the appearance of the building on the exterior was not an option. THERM software simulations were used to assess the performance improvement, and the glazing contractor provided feedback on installation practicalities.

Figure 4: THERM simulation outputs for the existing curtainwall system, the existing system with a VIG and the existing system with VIG and a thermally improved frame. Credit: WJE.

WJE’s THERM analysis showed the criticality of mitigating heat flow through the frame (see Figure 4). Swapping the 6 mm monolithic glass for VIG reduced the assembly U-factor by a factor of three (from 1.08 BTU/of.hr.ft2 to 0.33 BTU/of.hr.ft2), but it made no difference to the frame’s room-side temperature profile. The frame remained a cold spot, channeling heat flow to the exterior and at risk for condensation.

Thermally improving the frame, as well as the glass, reduced the assembly U-factor by a factor of six to a low 0.17 BTU/of.hr.ft2 and improved the room-side frame temperature substantially. This clearly demonstrates the large impact of edge and frame effects: Even though the glass was large, 6 feet 8 inches by 4 feet 8 inches, the edge effects from thermal bridging at the frame were still significant.

Figure 5: Plan view of the mullion retrofit. The custom polyamide extrusions are shown in dark gray. Credit: WJE.

The Polyamide Frame Insulation Solution

The final thermal retrofit design involved implementing custom polyamide (PA) extrusions (see Figure 5). They were designed to snap on the existing vertical U-channel to provide thermal isolation between these cold members and the interior section. Insulation was used to fill the cavity under the new room-side mullion cover.

PA was selected due to its ease of high-precision extrusion and its ability to be pre-cut without special handling requirements. The simple snap-in installation was also key to PA’s selection because of the tight extrusion tolerances. All these attributes of PA optimized fabrication and installation efficiencies. The PA profiles did not bear any load; their only purpose was for thermal isolation.

Sinusas and her team worked on the solution with Chad Ricker, technical expert and manager at Technoform North America, and his team. Ricker explained that innovations in PA tooling design have allowed for cost-effective low-volume solutions to be provided at short lead times for performance or visual mockups and single-project retrofits. In addition, the ability to create complex geometric shapes and hold extremely tight tolerances of at least +/- 0.05 mm makes PA an excellent option for retrofit frame improvements.

Figure 6: Polyamide pressure plates are an easy way of improving thermal performance in an existing pressure-plate curtainwall. Credit: Technoform.

For old pressure-plate curtain walls, one of the simplest ways of improving the frame performance is to exchange the aluminum pressure plates with non-metal pressure plates, such as those using PA (see Figure 6). Because of the ease of fabrication, PA plates can be pre-drilled and pre-cut, or this fabrication can be done in the field.

Takeaways

Retrofitting the glazing infill will make a significant impact on improving the thermal performance of a curtainwall. However, unless the frame is improved alongside the glass, the fenestration assembly will remain thermally leaky at the edges, and its condensation risk will not have markedly changed. There are now strategies to improve the frame using non-metal (PA) thermal barriers that can be more easily accessed for one-off retrofits because of technology and equipment enhancements. Having a wide range of cost-effective retrofit solutions that are available with a short lead time and easy to install is critical in reducing the barriers to window and façade retrofits.

One Reply to “Optimizing Façade Retrofits: Improve the Frame as Well as the Glass”

  1. there is another way that very nicely address’s old curtainwall systems with the structure on the outside and the glass on the inside. it addresses the thermal concerns of the frame. We have done it several times now

Leave a Reply

Your email address will not be published. Required fields are marked *

This site uses Akismet to reduce spam. Learn how your comment data is processed.