Size-Specific Fenestration Performance Rating: The Case for and Against

In the last year, there have been several lively discussions about providing architects, engineers and code officials with verified fenestration thermal and solar-optical performance based on project-specific sizes. The current certification standards from the National Fenestration Rating Council (NFRC) provide rated performance values based on a prescribed size only. There is a growing demand for reliable project size-specific performance data. This month, we dive into the arguments for and against providing size-specific values.

Background on Fenestration Performance Certifications

By way of background, NFRC has two fenestration certification programs:

  • A residential-style window labeling and certification program called the Product Certification Program or PCP. It is described in NFRC 700, and the output is a label affixed to a window containing performance data – U-factor, solar heat gain coefficient (SHGC), visible light transmission, air leakage and optionally, condensation resistance–all based on a standard size. While PCP-certified windows are mostly factory-built and used in single-family homes, they are also specified by architects in punched opening applications in light commercial and multi-family residential buildings.
  • A commercial fenestration rating program called the Component Modeling Approach Certification Program (CMA-CP), as described by NFRC 705. This program is tailored to the custom design needs of the commercial construction market and issues a label certificate for the fenestration instead of an adhesive label. It also provides certified thermal and solar-optical performance values based on a standard size.
NFRC label, an output of its Product Certification Program (PCP) used mainly for factory-built windows in single-family homes. Credit: NFRC.

The CMA-CP will be replaced shortly by a faster, easier and less expensive method called the Commercial Trendline Approach (CTA). It is described in NFRC 715, which will be published when the program is launched. This should go a long way toward reducing the barriers to adopting the CMA-CP because it eliminates the need to do physical testing for custom curtainwall and provides an easier way of deriving performance data for the many thousands of combinations of glass, spacer and frame.

In recognition of the commercial market need, both NFRC’s CMA-CP and CTA commercial programs allow project size-specific performance values to be provided on the label certificate, but for information purposes only.

Size-Specific Performance Calculations

NFRC provides methods to calculate size-specific performance data in the appendices of NFRC 100 Procedure for Determining Fenestration Product U-factors and NFRC 200 Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence. These require simulations to be done by an NFRC-accredited laboratory and can only be used for information purposes, not for code compliance.

The new CTA approach has a simpler way of determining size-specific data based on an aspect ratio calculation.

The Case for Project-Specific Size Performance Ratings

The actual thermal and solar control performance of a window depends on its size: A fenestration assembly’s U-factor and SHGC are area-weighted averages of the frame, edge of glass and center of glass performance. The assembly’s U-factor improves as the window increases because the frame-to-glass area reduces. Conversely, as an assembly’s size increases, its SHGC typically increases because of increasing glass area.

The actual impact of the window in a building, therefore, depends significantly on its actual size-based performance, not its labeled performance. Using size-based performance is critical to sizing heating and air-conditioning systems effectively to avoid both overheating and thermal discomfort from cold perimeter zones.

To support interior comfort and efficient HVAC systems, building energy modeling must also become more accurate to achieve net-zero emissions performance and to future-proof new buildings. The growth of existing building performance standards (BPS), such as Local Law 97 in New York City, is driving design teams to improve the prediction capability of building simulations. They are motivated to reduce the risk that their newly constructed buildings will not meet the BPS emissions targets. Having more accurate fenestration performance inputs is a key area of improvement.

Building performance standards, examples of outcome-based carbon emissions policy, are growing across the U.S. These require building energy simulations to become more predictive, which rely on more accurate fenestration performance input. Credit: U.S. Department of Energy, Building Technologies Office.

In the International Energy Conservation Code, it is unclear what inputs should be used for compliance path energy simulations. In practice, simulators use either standard or project-specific size data, depending on which is most beneficial to the code compliance outcome. This is a loophole in the compliance system that needs to be closed.

The City of Vancouver has developed standardized building energy modeling procedures to support code compliance, reduce gaming and improve accuracy. They require simulators to use project size-specific performance data for fenestration and need verified data to support compliance confirmation.

NFRC’s CMA-CP allows for project-specific size data to be provided for informational purposes, such as for building energy modeling. This is a good first step, but the label certificate boilerplate language states that the data cannot be used for code compliance, which can confuse code officials.

Moreover, for factory-built windows following NFRC’s PCP approach (with an affixed label), typically, no additional project size-specific data is provided, even for informational purposes. This could be a problem for designers of light commercial or mid-rise multi-family projects using these types of products, especially if performance path code compliance is chosen.

According to NFRC staff, requests for easy-to-obtain, verified, project-specific size information have been growing. Jillian Burgess, a building enclosure consultant from RDWI’s Philadelphia office, spoke during a spirited discussion of this issue at the NFRC Fall Membership Meeting. She underscored the need for design professionals like herself to have NFRC-verified size-specific data that can be shown to code officials to demonstrate compliance for performance path simulations.

The City of Vancouver’s building energy code has only a performance compliance path and requires project-specific window sizes for the building simulation. Credit: Photo by Albert Stoynov on Unsplash.

The Case Against Project Size-Specific Ratings

Having performance ratings based on a standardized fenestration size allows the consumer, builder or building designer to make easy apples-to-apples performance comparisons between fenestration systems. The NFRC labeling system has made a significant impact on the residential window market by providing this transparency. Its rating system has also facilitated the very successful ENERGY STAR® window program, which needed such a system to provide a basis for verifying and comparing performance.

A label with single-size performance values also makes it easy for code officials to verify compliance with prescriptive code requirements for fenestration.

Residential-style window manufacturers following the PCP must affix an NFRC label to every window. Given the vast array of sizes in which each window type can be provided, many manufacturers believe such a requirement would be unmanageable. They argue that when differences in dimensions between windows are as small as fractions of an inch, the difference in performance is negligible. Even providing size-specific data outside of the label is construed as too cumbersome.

In addition to these objections, advocates of more stringent commercial building energy codes were concerned that allowing performance path compliance using actual size-based performance could allow a backsliding performance by using poorer performing components in larger windows to meet the prescriptive code U-factor requirement. However, this would likely raise the SHGC and cause a compliance challenge.

The Nuances of Rating and Verification

There is clearly a need to have credible, easily verified, project-specific performance data for better building design and code compliance, especially in the non-residential and multi-family markets. The challenge is how to do so without causing unintended consequences that challenge the comparability provided by the current rating system and without imposing undue hardship on fenestration manufacturers.

Having listened to both sides of the argument, I wonder if the solution lies in interpreting the word “rating.” Perhaps we should consider data verification rather than performance rating for project-specific size performance.

A certified rating system classifies relative performance levels, assured by an independent third party. Rating systems should therefore allow apples-to-apples comparisons. It stands to reason that for fenestration, the performance should be based on standard sizes.

In contrast, verification is a process of establishing the accuracy of data. For use in building simulation and performance path code compliance, perhaps the provision of third-party verified,size-specific performance values (not ratings) and existing size-specific ratings could be part of the solution.

Size-specific performance values would need to be independently verified to provide credibility for performance path calculation inputs and code official sign-off, but they wouldn’t be a rating like the product’s standard size performance rating. Instead of being labeled for “information only,” can size-specific data, if third-party verified, be described specifically for building simulation and performance path code compliance validation?

There is already a framework in the NFRC’s new CTA to take this step, as it already includes size-specific performance and the regular standard size rating. However, there is no obvious solution to easily provide project-specific performance data using the NFRC’s regular PCP, where certified performance labels are affixed on unit windows before they leave the factory.

A new NFRC task group has been formed to address these questions, and I am hopeful that a solution will be found that supports providing verified accurate inputs for the design of high-performance buildings and also maintains the credibility of the NFRC fenestration rating system.